aHR0cDovL2ZyZWVzaGlwLmNvLmty
- ºê·£µå À̸§: ONEGOL
- À¯Çü: ´©Àü Â÷´Ü±â
- ±Ù¿ø: CN (Á¤Ç°)
- ¸ÂÃã °¡´É À¯¹«: ±×·¸½À´Ï´Ù
- ¸ðµ¨ ¹øÈ£: 98-16A
- ½º¸¶Æ® ±â±â: no
- Áõ¸í¼: Ul,KC,¼¼·ý
- Current rating range: 5~30A
- Input voltage rating: 125/250VAC; 32/50VDC
- Insulation co-ordination: Interrupting Capacity
Product Description Technical data Current rating range:3~50A Input voltage rating:125/250VAC; 32/50VDC Interrupting Capacity : 125/250VAC x 1,000A(UL 1077) Typical life :1,000 operations at 200% overload1,000 operations at 200% overload Insulation co-ordination:Rated impulse withstand voltage 2.5kV Rated impulse withstand voltage 2.5kV Dielectric Strength:> 1.500VAC/min. Insulation Resistance:>100MOHM (DC 500V) Degree of protection:Terminal area IP00, operating area IP40
Mechanical/Environmental Data Operating Ambient Temperature: -10¡É to +60¡É Mounting: Various options. See Ordering Information and drawings Termination: 250''(6.35mm)quick connects or solder terminals
Calibration(at25¡É) 100% of Rated Current: Hold , No Trip 300% of Rated Current: 1.5-5.0 sec Trip 200% of Rated Current: 5-30 sec Trip 150% ofRated Current: Trip Within 1 Hour
Approval Approval & File No. Rated current Rated voltage CUL UL E155159 3-50A 125/250VAC; 50VDC TUV SUD B15 09 58611 007 3-30A 125/250VAC; 32VDC CCC 201101030752058 3-30A 125/250VAC. VDE 40036160 3-16A 125/250VAC CSA 102199 3-30A 125VAC
Typical applicationsTypical applications Tarnsforms, Motors, Battery chargers, Power supplies appliances, extra low voltage systems, machineryappliances, extra low voltage systems, machinery Related Products
|
|
|
|
|