- Product Name: Photovoltaic MCB Auto Recloser
- Recloser Voltage Range: AC220V
- Function: Overvoltage,undervoltage,voltageloss,overload short circuit protection
GYRD9L-PV ÀÚµ¿ ¸®Å¬·Î¡ ¼ÒÇü ȸ·Î Â÷´Ü±â ž籤¹ßÀü ½Ã½ºÅÛ 6KA °úÀü¾Ð º¸È£ 63A-125A
In case of unwanted tripping after an electrical fault
General
GYRD9L-125 series photovoltaic special reclosing miniature circuit breaker, suitable for the line of AC 50Hz,rated workingvoltage to 400V, rated current to 125A with overvoltage, undervoltage,voltage loss, overload short circuit protection function. At present, broadly used in photovoltaic distributin box. Overvoltage 285±V, undervoltage 150V±5V. About 30 seconds after the product is powered on with normal voltage, it will automatically reset when the detected voltage is normal. It cannot be closed with a single flash during overvoltage, and it cannot be closed with double flashes during undervoltage. Overvoltage protection: Trip after overvoltage of 285±5V and last for 1 second. After tripping, if the voltage returns to normal voltage of 275V±5V and lasts for 30 seconds, it will be closed. Under-voltage protection: The under-voltage is 150V±5V and it will trip after 1 second. After the trip, if the voltage returns to the normal voltage of 160V±5V, it will be closed for 30 seconds. Loss of voltage protection: The normal voltage drops below 110V for more than 0.5 seconds, and it will trip directly. At this time, it cannot be manually closed.
|
|
|
|
|